What NFPA 96 covers
NFPA 96 is the National Fire Protection Association's standard for ventilation control and fire protection of commercial cooking operations. It covers the hood, filters, ducts and exhaust fan that carry grease-laden air out of a kitchen.
Airtech's kitchen exhaust work follows NFPA 96 guidance. The intervals below come from NFPA 96 (2024), Table 12.4.
The inspection schedule
| Type of cooking | Examples | Inspect at least |
|---|---|---|
| Solid fuel cooking | Wood or charcoal fired ovens and grills | Every month (monthly) |
| High-volume cooking | 24-hour cooking, charbroiling and wok cooking | Every 3 months (quarterly) |
| Moderate-volume cooking | Between the high and low volume classes; your authority having jurisdiction confirms the class | Every 6 months (semiannually) |
| Low-volume cooking | Churches, day camps, seasonal businesses and senior centres | Every year (annually) |
These are minimum inspection intervals for the exhaust system. Your authority having jurisdiction, insurer or the grease found on inspection can require cleaning sooner.
The inspection decides when to clean
The table sets how often the system is inspected for grease buildup. Cleaning follows when the inspection finds grease deposits (NFPA 96, section 12.6). A busy kitchen can need cleaning sooner than its class suggests.
Your authority having jurisdiction or your insurer can also ask for more frequent inspection or cleaning.
Find your interval
Type of cooking
Minimum inspection interval
Every 6 months
NFPA 96 term: Semiannually
These are minimum inspection intervals for the exhaust system. Your authority having jurisdiction, insurer or the grease found on inspection can require cleaning sooner.
Source: NFPA 96 (2024), Table 12.4
What an inspection records
Every job opens and closes with a RoboCam pass. You see the inside of your own duct, before and after, instead of taking our word for it.
01
Insert
RoboCam enters through an access port and records the duct as found.
02
Inspect
Photos and SD-card video fix the before-state, so the scope is based on evidence.
03
Clean
Negative pressure captures what the rotary brush and Air Whip release.
04
Verify
A second pass records the after-state for the report and the certificate.