NFPA 96 kitchen exhaust inspection intervals, explained

How often NFPA 96 says a commercial kitchen exhaust should be inspected, why the inspection decides when it is cleaned, and how to find your class.

Updated 7 November 2026 · 2 min read

What NFPA 96 covers

NFPA 96 is the National Fire Protection Association's standard for ventilation control and fire protection of commercial cooking operations. It covers the hood, filters, ducts and exhaust fan that carry grease-laden air out of a kitchen.

Airtech's kitchen exhaust work follows NFPA 96 guidance. The intervals below come from NFPA 96 (2024), Table 12.4.

The inspection schedule

Minimum inspection intervals for grease buildup, NFPA 96 (2024), Table 12.4
Type of cookingExamplesInspect at least
Solid fuel cookingWood or charcoal fired ovens and grillsEvery month (monthly)
High-volume cooking24-hour cooking, charbroiling and wok cookingEvery 3 months (quarterly)
Moderate-volume cookingBetween the high and low volume classes; your authority having jurisdiction confirms the classEvery 6 months (semiannually)
Low-volume cookingChurches, day camps, seasonal businesses and senior centresEvery year (annually)

These are minimum inspection intervals for the exhaust system. Your authority having jurisdiction, insurer or the grease found on inspection can require cleaning sooner.

The inspection decides when to clean

The table sets how often the system is inspected for grease buildup. Cleaning follows when the inspection finds grease deposits (NFPA 96, section 12.6). A busy kitchen can need cleaning sooner than its class suggests.

Your authority having jurisdiction or your insurer can also ask for more frequent inspection or cleaning.

Find your interval

Type of cooking

Minimum inspection interval

Every 6 months

NFPA 96 term: Semiannually

These are minimum inspection intervals for the exhaust system. Your authority having jurisdiction, insurer or the grease found on inspection can require cleaning sooner.

Source: NFPA 96 (2024), Table 12.4

What an inspection records

Every job opens and closes with a RoboCam pass. You see the inside of your own duct, before and after, instead of taking our word for it.

  1. 01

    Insert

    RoboCam enters through an access port and records the duct as found.

  2. 02

    Inspect

    Photos and SD-card video fix the before-state, so the scope is based on evidence.

  3. 03

    Clean

    Negative pressure captures what the rotary brush and Air Whip release.

  4. 04

    Verify

    A second pass records the after-state for the report and the certificate.